Type: ESX10-TB-DC24V-16A

Description

80 mm
Typ ESX10-TB-101-DC24V-16A von E-T-A: erweitert die Produktgruppe »ESX10-T.-DC24V«

The ESX10-TB-101-DC24V-16A is an extension of the ESX10-T range for DC24V and is the first product to complete a comprehensive protection range with ratings from 0.5 A to 16 A.

At a width of only 12.5mm it provides selective protection for all DC 24 V load circuits. This is achieved by a combination of active ­electronic current limitation in the event of a short circuit and overload disconnection typically from 1.15 times rated current. The ESX10-T is track-mountable and provides ease of installation for groups of ­devices with several circuits.

Voltage rating
Voltage rating
Rated voltage 16 A
Number of poles 1-pole
Load disconnection short circuit: typically 100 ms
overload: typically 220 ms
Current limitation typically 1,15 x IN
Status indication 1 LED green/orange/red: status/fault
Temperature range
Terminal design screw terminals
Certificates CE-logo UL 2367, File # E306740 Solid State Overcurrent Protectors

Applications

  • Automation
  • Automobile production
  • Chemical, Oil & Gas
  • Mechanical engineering
  • Pharmaceutical & Food
  • Power Engineering DC 24 V

Downloads

Datasheet & Explanations

Resources:

Improve Plant Production by Addressing 24VDC Switch-Mode Power Supply Issues

For most industries, the accepted norm for unplanned downtime is 5% of operating time, which represents a direct, significant loss of revenue and therefore profit. But have you ever stopped to consider the true cost of downtime?  Read the latest white paper from E-T-A to see how the integration of electronic circuit control technology can reduce the downtime of your 24VDC system designs.

Read White Paper

Utilizing Class I Div. 2 Circuit Breakers in Liquid Natural Gas Applications

An increase in the demand for energy worldwide has driven the search for alternative primary sources of energy, even to the most remote locations of the globe.  Natural gas is considered the cleanest burning fossil fuel with minimal environmental impact.   This white paper shares a real world example of how the integration of electronic circuit protection eliminates the need for widely used NEMA 7 enclosures.

Read White Paper

Virtual Assistant
Quickselect: Products Jobs Support About E-T-A
Call An Expert
Sie haben Fragen, Anregungen oder Wünsche? Wir beraten Sie gerne.