Type: ESS1      Download
 
Dimensions
 
   
The electronic circuit breaker ESS1 is designed to ensure selective disconnection of individual loads in industrial systems which are powered by a DC 24 V switch mode power supply.

Selectivity means that the ESS1 responds faster to overload or short circuit conditions than the power supply.
 
Voltage rating: 
DC 24 V (18...32 V)
Current ratings: 
3 A / 6 A selectable
Number of poles: 
1-pole 
Load disconnection: 
short circuit: typically100 ms
overload: typically 5 s 
Current limitation: 
max. 2 x IN 
Signal output: 
DC 30 V/1 A max.
Status indication: 
1 LED green: O.K. signal
4 LEDs yellow: load current indication
1 LED red: short circuit, overload (tripped) 
Temperature range: 
0...+40 °C
Terminal design: 
blade terminals 6.3 mm 
Mounting method:
plug-in for distribution system SVS1