Single pole thermal circuit breaker with push-to-reset, tease-free, trip-free, snap action mechanism (R-type TO CBE to EN 60934; M-type when fitted with optional manual release feature). Available in versions for plug-in or integral mounting, track mounting, or with a frame for snap-in panel mounting. The optional KF housing is particularly suited to high humidity and other damp conditions.
Approved to CBE standard EN 60934 (IEC 60934). |
| |
| Voltage rating: |
- AC 250 V
- DC 28 V
- UL: DC 50 V
|
| Current ratings: |
from 0.05 A to 25 A
|
| Number of poles: |
single pole
|
| Mounting method: |
flange socket rail mounting
|
| Terminal design: |
blade terminals screw terminals
|
| Actuation: |
manual release push button
|
| Auxiliary contacts: |
without auxiliary contacts
|
| Water splash protection: |
without water splash protection
|
| Illumination: |
without illumination
|
| Typical life: |
0.05...16 A 5,000 operations at 2 x IN, inductive
17...25 A 5,000 operations at 2 x IN, resistive |
| Interrupting capacity Icn: |
type F:
0.05...2.5 A. 8 x IN
3...5 A: 20 x IN
6...12 A: 200 A
13...25 A: 400 A
type T:
0.05...2.5 A: 8 x IN
3...5 A: 20 x IN
6...25 A: 400 A |
| Approvals: |
VDE, CSA, UL, CCC