Type: 2210-S291      Download
 
Dimensions
 
Internal connection diagrams
   
Single pole thermal-magnetic circuit breaker with trip-free mechanism and toggle actuation. Two-chamber construction with cascade contact arrangement to provide high voltage DC capability and high switching performance.
Designed for plug-in mounting in distribution rail X2210-S0606J or terminal blocks 23-P10-Si-202005 and 63-P10-Si-202005.
Approved to CBE standard EN 60934 (IEC 60934).
 
Voltage rating: 
  • AC 250 V
  • DC 65 V
Current ratings: 
from 0.4 A to 25 A  
Number of poles: 
single pole 
Mounting method: 
socket 
Terminal design: 
blade terminals 
Actuation: 
manual release 
toggle/baton 
Auxiliary contacts: 
with auxiliary contacts 
Water splash protection: 
without water splash protection 
Illumination: 
without illumination 
Typical life:
> 10,000 operations at 1 x IN
> 20,000 operations mechanical
Interrupting capacity Icn:
2210-S2..-...-410033:
AC 250 V 1000 A
DC 65 V 2000 A
2210-S2..-...-410005:
AC 250 V:
0.4...1 A: self-limiting
1.6...25 A: 2 000 A
DC 65 V:
0.4...4 A: self-limiting
6...25 A: 3 500 A
Approvals:
GL, VDE