| Dimensions |
 |
| |
| Internal connection diagrams |
 |
|
|
One, two and three pole thermal-magnetic circuit breakers with trip-free mechanism and toggle actuation (S-type TM CBE to EN 60934/IEC 934). Featuring a combi-foot design for both symmetric and asymmetric rail mounting. Available with auxiliary contact (1 x N/O or 1 x N/C) for status signalling. Two and three pole models are internally linked to ensure that both/all poles trip in the event of an overload on one pole, even if the actuator is held in the ON position. This CBE can be supplied in current ratings up to 32 A with a choice of characteristic curves. All screw terminals are recessed for safety.
Approved to CBE standard EN 60934 (IEC 60934). |
| |
| Voltage rating: |
- 3 AC 433 V (50/60 Hz)
- AC 250 V
- DC 65 V (higher voltage to special order)
- UL/CSA: AC 277 / 480 V
|
| Current ratings: |
from 0.1 A to 32 A for curves M1, T1, T2 (32 A resistive load only) from 0.1 A to 16 A for curves F1, F2, M3
|
| Number of poles: |
single pole double pole three pole
|
| Mounting method: |
rail mounting
|
| Terminal design: |
screw terminals
|
| Actuation: |
manual release toggle/baton
|
| Auxiliary contacts: |
with auxiliary contacts without auxiliary contacts
|
| Water splash protection: |
without water splash protection
|
| Illumination: |
without illumination
|
| Typical life: |
| 10,000 operations at 1 x IN, inductive |
| Interrupting capacity Icn: |
0.1...5 A: 400A
6...32 A: 800 A
cuve T2: 0.1...32 A: 15 x IN
curve M3: 0.1...2 A: AC 200 A / DC 400 A |
| Approvals: |
| GL, VDE, CSA, UL |
|