Safety in illumination


IIllumination technology always requires special solutions to ensure electrical safety.

Benefit from our long-standing expertise in this field!


Do you have any questions regarding this topic? Our specialists from the Equipment division will be pleased to be of assistance!


Below please find a list of relevant products for your business field. By selecting products out of a category you will be able to directly compare their technical specifications.

Just click on “product comparison".


Type: 1110      Download
 
Dimensions
 
Internal connection diagrams
   
Single pole switch/thermal circuit breaker (S-type TO CBE to EN 60934) with tease-free, trip-free, snap action mechanism. Designed for snap-in panel mounting utilising round hole or industry standard fuse-holder cut-out dimensions. Featuring an ergonomically styled two colour actuator with indicator band clearly showing the tripped/OFF position.
Approved to CBE standard EN 60934 (IEC 60934).
 
Voltage rating: 
  • AC 250 V
  • DC 28 V
  • UL/CSA: DC 50 V
Current ratings: 
from 0.05 A to 16 A  
Number of poles: 
single pole 
Mounting method: 
flange 
Terminal design: 
blade terminals 
Actuation: 
push button 
Auxiliary contacts: 
without auxiliary contacts 
Water splash protection: 
with water splash protection 
without water splash protection 
Illumination: 
without illumination 
Typical life:
0.05...10 A: 10,000 operations at 1 x IN, inductive
12...16 A: 6,000 operations at 1 x IN, inductive
Interrupting capacity Icn:
AC 250 V:
0.05...16 A: 8 x IN
DC 28 V:
0.05...6 A: 10 x IN
7...10 A: 200 A
12...16 A: 400 A
Approvals:
VDE, CSA, UL