| Dimensions |
 |
| |
| Internal connection diagrams |
 |
|
|
One, two and three pole thermal-magnetic circuit breakers with trip-free mechanism and toggle actuation (S-type TM CBE to EN 60934/IEC 934). Designed for panel or plug-in mounting. Available with auxiliary contacts (1 x N/O, 1 x N/C) for status signalling. Two and three pole models are internally linked to ensure that both/all poles trip in the event of an overload on one pole, even if the actuator is held in the ON position. A choice of characteristic curves further extends the range of applications possibilities for these CBEs. Special auxiliary contact versions for industrial atmosphere and low voltages (e.g. 5 V) available on request.
Approved to CBE standard EN 60934 (IEC 60934).
Suitable for use in distribution rails. |
| |
| Voltage rating: |
- 3 AC 433 V (50/60 Hz)
- AC 250 V
- DC 65 V (higher voltage to special order)
- UL: AC 277 V
|
| Current ratings: |
from 0.1 A to 25 A curves M1, T1, T2 from 0.1 A to 16 A curves F1, F2, M3
|
| Number of poles: |
single pole double pole three pole
|
| Mounting method: |
socket
|
| Terminal design: |
blade terminals
|
| Actuation: |
manual release toggle/baton
|
| Auxiliary contacts: |
with auxiliary contacts without auxiliary contacts
|
| Water splash protection: |
with water splash protection without water splash protection
|
| Illumination: |
without illumination
|
| Typical life: |
| 10,000 operations at 1 x IN, inductive |
| Interrupting capacity Icn: |
0.1...5 A: 400 A
6...25 A: 800 A
curve T2: 0.1...25 A: 15 x IN
curve M3: 0.1...2 A AC 200 A / DC 400 A |
| Approvals: |
| GL, VDE, CSA, UL |
|