Cellular phone networks, internet, access, transmission and switching technology – we have the perfect solution for these applications. Of course we can also offer suitable protection for any other component used in the telecommunications industry.
Do you have any questions regarding this topic? Our specialists from the Telecommunication division will be pleased to be of assistance!
Below please find a list of relevant products for your business field. By selecting products out of a category you will be able to directly compare their technical specifications.
Just click on “product comparison".
| Type: 2210-S291 |
|
Download |
 |
| |
| Dimensions |
 |
| |
| Internal connection diagrams |
 |
|
|
Single pole thermal-magnetic circuit breaker with trip-free mechanism and toggle actuation. Two-chamber construction with cascade contact arrangement to provide high voltage DC capability and high switching performance.
Designed for plug-in mounting in distribution rail X2210-S0606J or terminal blocks 23-P10-Si-202005 and 63-P10-Si-202005.
Approved to CBE standard EN 60934 (IEC 60934). |
| |
| Voltage rating: |
|
| Current ratings: |
from 0.4 A to 25 A
|
| Number of poles: |
single pole
|
| Mounting method: |
socket
|
| Terminal design: |
blade terminals
|
| Actuation: |
manual release toggle/baton
|
| Auxiliary contacts: |
with auxiliary contacts
|
| Water splash protection: |
without water splash protection
|
| Illumination: |
without illumination
|
| Typical life: |
> 10,000 operations at 1 x IN
> 20,000 operations mechanical |
| Interrupting capacity Icn: |
2210-S2..-...-410033:
AC 250 V 1000 A
DC 65 V 2000 A
2210-S2..-...-410005:
AC 250 V:
0.4...1 A: self-limiting
1.6...25 A: 2 000 A
DC 65 V:
0.4...4 A: self-limiting
6...25 A: 3 500 A |
| Approvals: |
| GL, VDE |
|