The electronic E-T-A Voltage Monitor E-1079-60. is designed to monitor DC or AC voltages against falling below, or rising above, preset tolerance limits. Two LEDs indicate relay status or overlimits; an opto coupler output provides a physically isolated signal.
The device is available either with a (non-conducting) N/O or a (conducting) N/C contact. It is powered by the measuring signal so that there is no need for an additional power supply. |
| |
| Voltage rating: |
AC 115 V = measuring range AC 230 V = measuring range DC 12 V = measuring range DC 24 V = measuring range DC 48 V = measuring range DC 110 V = measuring range DC 220 V = measuring range
|
| Supply voltage: |
DC 12 V +/-25% (9...15 V) DC 24 V +/-25% (18...30 V) DC 48 V +/-25% (36...60 V) DC 110 V +10%/-15% (93.5...121 V) DC 220 V +10%/-15% (187...242 V) AC 115 V +10%/-15% (97.8...126.5 V) AC 230 V +10%/-15% (195.5...253 V)
|
| Setting range/Measuring range: |
DC 12 V +/-25% DC 24 V +/-25% DC 48 V +/-25% DC 110 V +10%/-15% DC 220 V +10%/-15% AC 115 V +10%/-15% AC 230 V +10%/-15%
|
| Output: |
MOSFET output AC/DC 250 V / 80 mA
|
| Temperature range: |
from 0 °C to +60 °C
|
| Mounting method: |
plug-in type, suitable for on E-T-A socket type 17-P10-Si
|