Our circuit breakers for equipment protection protect, switch and monitor all kinds of components in industrial automation, from individual machine tools to complete assembly lines in the car manufacturing industry. Local and central control technology in the process control industry or field connection in power plants are typical applications of our versatile power distribution systems for DC24V or AC230V. They help to optimise design, wiring, function and maintenance of the entire electrical system.

Stoppages and downtimes will practically be reduced to zero.


Do you have any questions regarding this topic? Our specialists from the Automation & Process Control division will be pleased to be of assistance!


Below please find a list of relevant products for your business field. By selecting products out of a category you will be able to directly compare their technical specifications.

Just click on “product comparison".


Type: 2210-S291      Download
 
Dimensions
 
Internal connection diagrams
   
Single pole thermal-magnetic circuit breaker with trip-free mechanism and toggle actuation. Two-chamber construction with cascade contact arrangement to provide high voltage DC capability and high switching performance.
Designed for plug-in mounting in distribution rail X2210-S0606J or terminal blocks 23-P10-Si-202005 and 63-P10-Si-202005.
Approved to CBE standard EN 60934 (IEC 60934).
 
Voltage rating: 
  • AC 250 V
  • DC 65 V
Current ratings: 
from 0.4 A to 25 A  
Number of poles: 
single pole 
Mounting method: 
socket 
Terminal design: 
blade terminals 
Actuation: 
manual release 
toggle/baton 
Auxiliary contacts: 
with auxiliary contacts 
Water splash protection: 
without water splash protection 
Illumination: 
without illumination 
Typical life:
> 10,000 operations at 1 x IN
> 20,000 operations mechanical
Interrupting capacity Icn:
2210-S2..-...-410033:
AC 250 V 1000 A
DC 65 V 2000 A
2210-S2..-...-410005:
AC 250 V:
0.4...1 A: self-limiting
1.6...25 A: 2 000 A
DC 65 V:
0.4...4 A: self-limiting
6...25 A: 3 500 A
Approvals:
GL, VDE